Call Now: 1-800-284-2288 |
Uninterruptible Power Supply |
|
|
The CEN-UPS1250 is a 1250 Watt, 120 Volt uninterruptible power supply and power conditioner Engineered by APC® specifically for Crestron®. Designed to protect Crestron control systems, media servers, video displays and other devices, the CEN-UPS1250 employs pure sine wave battery backup to maintain continuous operation of critical components whenever power is disrupted. Remote monitoring and control through award-winning Crestron RoomView® software, and full Crestron control system integration, deliver a comprehensive power management and protection solution that's an integral part of the complete Crestron control network.
Available Configurations Include:
CEN-UPS1250-BTP | Internal Battery Pack for CEN-UPS1250 |
CEN-UPS1250 features include:
UPS/Power Conditioner | ||
Output Power Capacity | 1250 Watts (1440 VA) @120 Volts AC nominal | |
Efficiency | 90% at full load | |
Output Voltage Distortion | <5% at full load | |
Output Frequency | 47 to 63 Hz (sync to line power input) | |
Waveform Type | Sine wave | |
Transfer Time | 7mS typical, 10mS maximum during blackout | |
Power Line Surge Protection | Rated for 4080 Joules | |
Filtering | Full-time multi-pole noise filtering, 5% IEEE surge let-thru, zero clamping response time, meets UL 1449 Dataline protection | |
Voltage Regulation | Performs voltage boost or trim to maintain 120V nominal output | |
Maximum Output Current | 12 Amps per outlet, 12 Amps total | |
Power Requirements | ||
Input Voltage | 92 to 142 Volts AC, 120 Volts nominal | |
Input Frequency | 47 to 63 Hz | |
Maximum Input Current | 12 Amps (when fed from 15 Amp circuit) | |
Battery | ||
Internal Battery | (1) Crestron model CEN-UPS1250-BTP battery pack included, composed of (4) 12 Volt, 9Ah maintenance-free sealed lead-acid w/suspended electrolyte batteries | |
Backup Runtime | ~12 minutes @ half load (625W), ~2.7 minutes @ full load (1250W) | |
Recharging Time | ~8 hours typical to 90% capacity following a discharge to shutdown @ half load | |
Battery Life | 2 to 5 years under normal use | |
Ethernet | ||
10BaseT/100BaseTX, auto-switching, auto-negotiating, autodiscovery, full/half duplex, TCP/IP, UDP/IP, CIP, DHCP | ||
Connectors | ||
BANK 1 – DIGITAL DEVICES | (6) NEMA 5-15R female; Grounded AC power outlets, switched; Includes noise filtering and protection for digital devices such as control systems, power supplies, touchpanels, and media servers |
|
BANK 2 – DISPLAYS | (2) NEMA 5-15R female; Grounded AC power outlets, switched; Includes noise filtering and protection for display devices such as LCDs, plasmas, and projectors |
|
BANK 3 – ANALOG DEVICES | (2) NEMA 5-15R female; Grounded AC power outlets, delayed-switched; Delayed turn-on, adjustable 0 to 10 seconds; Includes noise filtering and protection for analog devices such as Adagio control systems and tuners |
|
BANK 4 – HI-CURRENT DEVICES | (2) NEMA 5-15R female; Grounded AC power outlets, delayed-switched; Delayed turn-on, adjustable 0 to 10 seconds; Includes noise filtering and protection for high-current devices such as amplifiers |
|
EXTERNAL BATTERY | (1) Connector for optional external battery, sold by APC[1] | |
SERVICE PORT | (1) USB Type B female; Used for factory configuration only |
|
TELCO IN | (1) 4-pin RJ11 female; Dual-line telephone line connection |
|
TELCO OUT | (2) 4-pin RJ11 female; Protected dual-line telephone/modem device connections |
|
CABLE IN | (1) F-type coaxial, female; Coaxial cable or antenna source connection |
|
CABLE OUT | (1) F-type coaxial, female; Protected TV/receiver or modem device connection |
|
SATELLITE IN | (1) F-type coaxial, female; Coaxial cable or antenna source connection |
|
SATELLITE OUT | (1) F-type coaxial, female; Protected TV/receiver or modem device connection |
|
COMPUTER | (1) USB Type B female; USB computer console port (cable included) |
|
LAN | (1) 8-wire RJ45 with 2 LED indicators; 10/100BaseT Ethernet port; Green LED indicates link status; Yellow LED indicates Ethernet activity |
|
G | (1) Binding post, chassis ground lug | |
INPUT 120V 47-63Hz 12A | (1) IEC-320 C14 chassis plug; Line Power Input, mates with 10 ft (3.05 m) power cord, included |
|
ENV PROBE | 6-pin mini-DIN, female; Connection for external temperature/RH sensor, included |
|
Buttons | ||
STATUS | (1) Sequences through display of various electrical and environmental measurements, operational status, battery condition and other system information | |
SETUP | (1) Sequences through various configuration settings and operations | |
Λ, V | (2) Used to adjust configuration settings up/down or on/off | |
Power/Standby | (1) Turns all output banks on or off, forces cold-start to battery when held | |
CIRCUIT BREAKER (rear) | Disrupts power to all outputs in case of an overload condition, press to reset | |
RESET (rear) | (1) Red miniature pushbutton, resets communications board | |
Display | ||
Vacuum fluorescent, (2) lines, (20) characters per line | ||
LED Indicators | ||
BATT IN USE | (1 yellow) Indicates output power is being fed from battery backup | |
ON LINE | (1 green) Indicates a working connection to the control system | |
DELAY AMP | (1 green) Indicates the BANK 4 – HI-CURRENT DEVICES output bank is turned on | |
REGULATING | (1 green) Indicates voltage regulation is operating to compensate for a high or low line voltage condition | |
LOW BATT | (1 yellow) Indicates remaining backup time has fallen below a preset amount, adjustable from 2 to 26 minutes | |
AC PWR OK | (1 green) Indicates the line input voltage is within the acceptable operating range of 92V to 142V | |
FILTERING | (1 green) Indicates that the EMI and RFI noise reduction circuit is active | |
OVERLOAD | (1 red) Indicates there is too much load connected to the output | |
WIRING FAULT (rear) | (1 red) Indicates a missing ground, overloaded neutral, or reversed polarity at the line power input | |
Alarm | ||
Audible alarm indicates when in backup mode, when battery is low, and when overloaded | ||
Environmental | ||
Temperature | 32° to 104°F (0° to 40°C) | |
Humidity | 10% to 90% RH (non-condensing) | |
Enclosure | ||
Chassis | Steel, black matte powder coat finish | |
Cooling | Microprocessor-controlled ultra-quiet rear-facing fan, vented sides | |
Faceplate | Extruded aluminum, black matte powder coat finish with polycarbonate label overlay | |
Mounting | Freestanding or 3U 19-inch rack-mountable, rack must be 4-post type up to 28-inch maximum depth (removable feet and rack mount kit included) | |
Dimensions | ||
Height | 5.54 in (141 mm); 5.21 in (133 mm) without feet |
|
Width | 17.02 in (433 mm); 19.11 in (486 mm) with ears |
|
Depth | 19.73 in (501 mm) | |
Weight | ||
62.0 lb (28.12 kg) |
cen-ups1250.pdf | Datasheet |
Call Now: 1-800-284-2288 |
|||||
Email Us: sales@avsupply |
|||||
|