Sectional Wall Mount Rack
|
The Middle Atlantic DWR-Series shall be constructed to
swing open for component cabling access, center section shall pivot for either left or
right opening.. Center section and back pan shall be 16-gauge steel,
phosphate pre-treated and finished in a black textured powder coat. Rackrail shall be
constructed of 11-gauge steel with tapped 10-32 mounting holes in universal EIA
spacing with black e-coat finish and marked rack spaces. Rack shall have a rear knockout panel with 1/2”, 3/4”, 1", 1-1/2”, 2”
and 3” electrical knockouts installed in base, and a rear knockout panel with 1/2”,
3/4”, 1”, 1-1/2”, 2” and 3” electrical knockouts, four Decora® cutouts, and BNC
knockouts for UHF/VHF antennas installed in top. Large laser knockout on back pan
shall have a 12-1/2” x 12-1/2” cutout for electrical pull-box. Fan knockouts on top
and bottom shall allow for installation of up to four 4-1/2" fans.
The DWR rack shall have 2”
knockouts, 4” knockouts for Wiremold 4000® Series raceways, and knockouts for UCP
Series universal connector panels on the side. Top, bottom and sides shall feature
vertical vent pattern. DWR Series enclosures shall satisfy the 2007 & 2010 CBC; 2006,
2009 & 2012 IBC; ASCE 7-05 (2005 Edition) & ASCE 7-10 (2010 Edition) and the 2006
& 2009 editions of NFPA 5000 for use in areas of high seismicity, Seismic Use Group III,
Zone 4 or Seismic Design Category (SDC) “D” with lateral force requirements for
protecting 140 lbs. of essential equipment in locations with the highest level of seismicity
and top floor or rooftop installations with an Importance factor (Ip) of 1.5 when used
with DWRSR-ZL Latch. Rack shall be UL Listed in the US and Canada. Rack shall be
DWR-24-22
US PATENT# 7, 278, 183 SEISMIC CERTIFIED EIA/TIA Compliant
Backpan Center Section
see inside for important information
regarding useable depths
GREENGUARD Indoor Air Quality Certified for Children and Schools. Rack shall be RoHS EU
Directive 2002 / 95 / EC compliant. Rack shall be manufactured by an ISO 9001 and ISO
14001 registered company. Rack shall be warrantied to be free from defects in materials
or workmanship under normal use and conditions for the lifetime of the rack.
→ Breakthrough design provides more useable rack height – for example, the 45 space version overall height is shorter than 44 space alternative models
→ Accepts patent-pending LeverLock™ system accessories for fast, flexible cable management and mounting of small devices such as interface boxes, power supplies, and relay modules
→ Unique new extender bay adds 3" of useable depth to the front or rear of the enclosure at any time. Extender bays allow the use of existing doors and can even be stacked for greater depths
→ Pre-threaded ganging holes allow ganging while fully loaded
→ Wide open bottom accepts multiple base options
→ Standard front and rear adjustable wide, heavy-gauge, 10-32 threaded rackrail with numbered rackspace increments speeds equipment mounting
→ Labels included to indicate rail position front to back
→ Finished in a durable black textured powder coat
→ UL Listed in the US and Canada
→ Tool-Free Quick-Mount™ system allows for easy, one-person mounting of the center section to the backpan on the jobsite
→ Available in 15”, 20”, 24" and 30” useable depths
→ Welded construction provides up to a 300 lb. weight capacity, depending on model
→ Abundant built-in cable lacing points in interior
→ ½”, 34”, 1”, 1 ½”, 2” and 3” electrical knockouts and 5/8” UHF/VHF antenna knockouts on top & bottom, easily removable for cable pass-through
→ 12 ½” x 12 ½” laser knockout opening in the backpan for electrical pull-box
→ Abundant Velcro and internal cable tie points
→ Finished in a durable black textured powder coat
→ Standard adjustable front 11-gauge 10-32 threaded rackrail with marked rackspace increments to speed equipment mounting
→ Center section hinges for left or right opening accessories
→ 2" knockouts, 4" knockouts for Wiremold® 4000 Series raceways, and knockouts for UCP series universal connector panels on side
→ Grounding/bonding stud in top and bottom of center section and backpan facilitates proper grounding and bonding of electronic equipment, as per NEBS and NEC standards
→ Front Mounted Minimum-Clearance Latch saves valuable wall space by allowing wall racks to be placed side-by-side, in a corner, or wherever side clearance is an issue.
Seismic certified to the following codes and standards | 2007 & 2010 CBC; 2006, 2009 & 2012 IBC; ASCE 7-05 (2005 Edition) & ASCE 7-10 (2010 Edition) |
and the 2006 & 2009 editions of NFPA 5000 for use in areas of high seismicity – Zone 4 or Seismic Design Category (SDC) "D". These are designed for Mission Critical and/or High-Importance Installations in locations with the highest level of seismicity and top floor or rooftop installations including those within UBC and CBC Essential facilities or IBC, ASCE 7, and NFPA 5000 Seismic Use Group III facilities. For all codes, the Importance factor (Ip) is 1.5. Seismic Certified load capacity of 140 lbs. when used with DWRSR-ZL Latch.